Technical note · August 2026

Power over Ethernet is now in the Wiring Regulations.


On 15 April 2026 the IET and BSI published BS 7671:2018+A4:2026. Among its changes is a new Section 716 covering Power over Ethernet, together with a new section on functional earthing and functional equipotential bonding for information and communication technology equipment. The previous edition is withdrawn on 15 October 2026.

This note sets out what that means in practice for anyone specifying, procuring or installing a network that carries power.

At a glance

  • StandardBS 7671:2018+A4:2026
  • Published15 April 2026
  • Prior edition withdrawn15 October 2026
  • New section716 — PoE
  • Also newFunctional earthing for ICT
  • Max PoE load90 W · 802.3bt Type 4

01 · Why it happened

Ethernet stopped being a signalling system.


When Power over Ethernet arrived it delivered 15.4 watts to a desk phone. That was a curiosity, not an electrical installation. Under IEEE 802.3bt Type 4, a single port now delivers up to 90 watts at the powered device, and a modern building distributes a great deal of its lighting, access control, surveillance, wireless and display estate over exactly that infrastructure.

A 48-port switch running Type 4 devices at capacity is distributing meaningful power through hundreds of small conductors bundled together in containment that was often sized for data alone. That is an electrical installation by any sensible reading, and the national wiring standard has now recognised it as one.

The practical consequence is straightforward: the design decisions that used to sit entirely with the data contractor now sit, at least partly, inside a standard that data contractors are not typically certified against.

The four PoE types

StandardTypeAt the device
802.3afType 112.95 W
802.3atType 225.5 W
802.3btType 351 W
802.3btType 471.3 W

Figures are the guaranteed minimum available at the powered device. Port output is higher — up to 90 W for Type 4 — with the difference dissipated as heat in the cable. That heat is the whole design problem.

02 · What actually changes

Five design decisions that are no longer discretionary.


None of these is new engineering. What is new is that they now sit within the scope of the national wiring standard, which changes who is accountable for getting them right and what evidence is expected at handover.

  1. Bundle size and temperature riseCurrent flowing in a conductor generates heat. In a bundle, the cables in the centre cannot dissipate it, so the bundle's core runs hotter than its surface. Above a certain temperature, insertion loss rises and the permissible channel length falls — which is how a compliant 90 metre design quietly becomes a non-compliant one. BS EN 50174-2 gives the bundle guidance; A4:2026 brings the electrical consequences into BS 7671's scope.
  2. Conductor size and cable constructionLarger conductor gauge carries the same current with less resistive heating. Screened constructions dissipate heat better than unscreened. Where PoE loading is high, the correct answer is frequently a better cable rather than a shorter run — but that is a cost decision somebody has to make deliberately and record.
  3. Containment fillFill percentages have traditionally been set so the cable physically fits and can be added to later. Under significant PoE load they must also permit heat to escape. A tightly packed basket is a thermal problem, not merely an untidy one.
  4. Functional earthing and equipotential bonding for ICTThe separate new section addresses earthing arrangements for information and communication technology equipment. In practice this covers cabinet earthing, containment bonding and the arrangements at the equipment itself — historically an area of considerable inconsistency between installations.
  5. Evidence at handoverWhere a design decision now falls within BS 7671, the expectation is that it can be evidenced. Load assumptions, bundle limits and earthing arrangements should be recorded rather than held in an engineer's head, particularly on any project inside the Building Safety Act's higher-risk regime, where the golden thread of information has been a legal duty since April 2024.

03 · The procurement question

Who signs the electrical element of your design?


This is the part worth thinking about before your next tender goes out. A structured cabling contractor without electrical certification is now, in substance, contributing to a design governed by a standard it is not certified against.

In most cases that will pass without incident, as it has for years. But on a project within the higher-risk building regime, or anywhere a duty holder must demonstrate that appointees have the necessary skills, knowledge, experience and behaviours, it becomes a question at Gateway rather than a snag at handover.

There is no requirement for a single contractor to hold both capabilities. There is a requirement for somebody competent to own the electrical element, and for that to be a documented arrangement rather than an assumption that the other party is dealing with it.

Ask your contractor these five

  • 01What PoE type and per-port load has the design been calculated against?
  • 02What bundle size limits have been applied, and to what standard?
  • 03Has the containment fill been set for thermal performance or only for physical fit?
  • 04Who is certifying the functional earthing and bonding arrangements?
  • 05Will the load assumptions be issued as part of the handover pack?

A contractor who can answer all five without hesitating has read the amendment. One who cannot has not.

04 · Common questions

Straight answers.


Does Amendment 4 mean an electrician has to install my data cabling?

No. It means the electrical aspects of a PoE installation fall within the scope of BS 7671, and that somebody competent must own them. A data contractor can install the cabling; what must be documented is who is accountable for the load calculation, the bundle limits, the containment thermal performance and the earthing arrangements. Where one organisation holds both competencies, that accountability is simply not divided.

When does the previous edition stop applying?

BS 7671:2018+A2:2022 incorporating A3:2024 is withdrawn on 15 October 2026. Installations designed before that date under the previous edition are not retrospectively non-compliant, but new design work from that point should be to A4:2026.

Does this apply to a small installation?

The standard applies regardless of size, but the practical significance scales with PoE loading. A handful of Type 1 devices on a short run presents essentially no thermal issue. Forty-eight Type 4 ports in a bundled riser is a different proposition entirely, and that is where the design attention belongs.

Do I need to change my existing installation?

Not because of the amendment alone. It is worth reviewing where PoE loading has increased materially since installation — a Wi-Fi 7 refresh, for example, typically moves access points from Type 2 to Type 3 or Type 4, which can change the thermal picture on cabling that was designed for a lighter load.

What else did Amendment 4 introduce?

Alongside Section 716 and the ICT functional earthing provisions, the amendment introduced a new section covering stationary secondary batteries, revised Section 710 for medical locations, and recognised protective neutral bonding arrangements. Section 716 is the change most relevant to network infrastructure.

How does this interact with the Building Safety Act?

Where a building falls within the higher-risk regime, duty holders must be able to demonstrate the competence of those appointed, and safety-relevant information must be maintained in the golden thread. A design decision now governed by BS 7671 is one a duty holder may reasonably be asked to evidence, which is an argument for recording the load assumptions rather than leaving them implicit.

Specification review

Written before April 2026?
We will mark it up free.


If you hold a cabling specification, performance schedule or framework rate card that pre-dates Amendment 4, send it over. We will review it against the current instrument set and return a marked-up commentary at no charge, with no obligation attached.*

0345 3 822 833
datacablers@segplc.com

This note is a plain-language summary prepared for clients and specifiers. It is not legal or design advice, does not reproduce the standard, and is not a substitute for the published text of BS 7671:2018+A4:2026, which should be consulted directly. Stated as at August 2026. Source: IET and BSI, publication of Amendment 4:2026 to BS 7671:2018, published 15 April 2026.