02 · Standards register
The instruments we design and test against.
This is the register referenced on our quotations. Where a client, landlord, insurer or consultant imposes an additional or alternative standard, we adopt it and record the substitution rather than quietly working to our own.
BS EN 50173 series
Generic cabling for customer premises
Defines the channel and permanent link classes — Class D through Class FA, and Class I / II for Category 8 — against which our copper performance is measured. Part 5 addresses cabling for data centre spaces specifically.
BS EN 50174-1 / -2 / -3
Installation planning, practice & quality assurance
Specification and administration including labelling and record keeping; installation practice inside buildings, covering separation from power supplies and bundle limits for Power over Ethernet heat rise; and installation outside buildings for external and inter-building routes.
BS 6701:2016+A1:2017
Telecommunications equipment and cabling — installation, operation and maintenance
The UK installation benchmark for telecommunications cabling. It recommends a minimum reaction-to-fire performance of Euroclass Cca-s1b,d2,a2 for installation cables routed within the external fire barrier of a building. We specify to that recommendation as our default position and depart from it only on a written instruction that records the reason.
Construction products · reaction to fire
Euroclass, Declarations of Performance & the 2026 reform programme
Great Britain sets no single statutory Euroclass minimum for general building cables, so the class is specification-driven and risk-driven. We set it against the building's fire strategy, the BS 6701 recommendation and any client or insurer requirement, and we record the Declaration of Performance and Euroclass in the handover pack.
Current position. CE-marked construction products remain accepted for placing on the GB market. The Government's Construction Products Reform White Paper consultation ran from 25 February to 20 May 2026, proposing a risk-based General Safety Requirement; BSI published PAS 2000:2026 in March 2026 as a supporting framework. We track this programme and will update client specifications as the regime is implemented.
BS 7671:2018+A4:2026
Requirements for Electrical Installations — IET Wiring Regulations
Applies wherever our work touches the fixed electrical installation: containment, bonding, segregation, cabinet and comms room supplies, and now Power over Ethernet under Section 716 and functional earthing for ICT systems. Regulation 527.1.3 ties cable selection to reaction-to-fire performance.
IEC 61935-1 & IEC 61280-4
Field testing of balanced cabling and fibre links
The methods and limits behind every certificate we issue. Copper to IEC 61935-1, or to ANSI/TIA-1152-A where a client standard requires the TIA method. Fibre insertion loss to IEC 61280-4-1 (multimode) and IEC 61280-4-2 (singlemode), with Tier 2 OTDR where specified.
Building Safety Act 2022
Higher-risk buildings, duty holders and the golden thread
The higher-risk building regime applies to buildings at least 18 metres in height or of at least seven storeys containing two or more residential units, and to hospitals and care homes meeting the height threshold. The golden thread of information has been a legal duty since April 2024, and Gateway approvals apply at planning, pre-construction and completion.
Where we work in scope, our test records, product traceability, fire stopping evidence and as-installed information are produced in a form that hands directly into the golden thread. This is a specification and cost decision made at tender stage; retrofitting the evidence after completion is materially more expensive than collecting it as the work proceeds.
BS EN 1366-3 & BS 476-20
Fire resistance of service penetrations
Every penetration we form through a fire compartment is reinstated with a tested system, installed within the manufacturer's field of application, and photographed with its location reference before it is concealed. An unphotographed penetration is treated as an incomplete work item, not as a completed one.
BS EN 50600 & ISO/IEC 22237
Data centre facilities and infrastructures
Design, availability classification, physical security and operational process requirements for data centre facilities. Where a facility operates to an availability class or to a client standard such as ANSI/TIA-942, we build to that classification and evidence conformity in the handover record.
ISO/IEC 11801 series
International generic cabling
The international parent standard for the EN 50173 series, including the Class F / FA and Class I / II definitions. ISO/IEC TR 11801-9906:2025 addresses balanced single-pair cabling channels up to 600 MHz for Single Pair Ethernet, relevant to building services and industrial edge deployments.